Electricity meter

Uses your system voice; voice and rate in settings.

Snapshot

≈ 8 min read

Names in other languages

No names in other languages are held for this entry yet.

Article bodies are English and are not machine-translated. A name in another language is not a translation of the article.

) power meter in its meter base (located in Loveland, Colorado, USA). An electricity meter, electric meter, electrical meter, energy meter, kilowatt-hour meter, or power meter is a device that measures the amount of electric energy consumed by a residence, a business, or an electrically powered device over a time interval. Electric utilities use electric meters installed at customers' premises for billing and monitoring purposes. They are typically calibrated in billing units, the most common one being the kilowatt hour (kWh).

They are usually read once each billing period. When energy savings during certain periods are desired, some meters may measure demand, the maximum use of power in some interval. "Time of day" metering allows electric rates to be changed during a day, to record usage during peak high-cost periods and off-peak, lower-cost, periods. Also, in some areas meters have relays for demand response load shedding during peak load periods.

) power meter in its meter base (located in Loveland, Colorado, USA).]] An electricity meter, electric meter, electrical meter, energy meter, kilowatt-hour meter, or power meter is a device that measures the amount of electric energy consumed by a residence, a business, or an electrically powered device over a time interval. Electric utilities use electric meters installed at customers' premises for billing and monitoring purposes. They are typically calibrated in billing units, the most common one being the kilowatt hour (kWh).

They are usually read once each billing period. When energy savings during certain periods are desired, some meters may measure demand, the maximum use of power in some interval. "Time of day" metering allows electric rates to be changed during a day, to record usage during peak high-cost periods and off-peak, lower-cost, periods. Also, in some areas meters have relays for demand response load shedding during peak load periods. P = {{3600 \cdot Kh } \over t} . Where: = time in seconds taken by the disc to complete one revolution, = power in watts.

For example, if = 7.2 as above, and one revolution took place in 14.4 seconds, the power is 1800 watts. This method can be used to determine the power consumption of household devices by switching them on one by one. Most domestic electricity meters must be read manually, whether by a representative of the power company or by the customer. Where the customer reads the meter, the reading may be supplied to the power company by telephone, post or over the internet.

The electricity company will normally require a visit by a company representative at least annually in order to verify customer-supplied readings and to make a basic safety check of the meter. In an induction type meter, creep is a phenomenon that can adversely affect accuracy, that occurs when the meter disc rotates continuously with potential applied and the load terminals open circuited. A test for error due to creep is called a creep test. Two standards govern meter accuracy, ANSI C12.20 for North America and IEC 62053.

In Europe, Asia, Africa and most other locations, single phase is common for residential and small commercial customers. Single phase distribution is less-expensive, because one set of transformers in a substation normally serve a large area with relatively high voltages (usually 230 V) and no local transformers. These have a simple metering equation: Watts = volts x amps, with volts measured from the neutral to the phase wire.

In the United States, Canada, and parts of Central and South America similar customers are normally served by three-wire single phase. Three-wire single-phase requires local transformers, as few as one per ten residences, but provides lower, safer voltages at the socket (usually 120 V), and provides two voltages to customers: neutral to phase (usually 120 V), and phase to phase (usually 240 V).

Additionally, three-wire customers normally have neutral wired to the zero side of the generator's windings, which gives earthing that can be easily measured to be safe. These meters have a metering equation of Watts = 0.5 x volts x (amps of phase A − amps of phase B), with volts measured between the phase wires. Industrial power is normally supplied as three phase power. There are two forms: three wire, or four wire with a system neutral. In "three wire" or "three wire delta", there is no neutral but an earth ground is the safety ground.

The three phases have voltage only relative to each other. This distribution method has one fewer wire, is less expensive, and is common in Asia, Africa, and many parts of Europe. In regions that mix residences and light industry, it is common for this to be the only distribution method. A meter for this type normally measures two of the windings relative to the third winding, and adds the watts.

One disadvantage of this system is that if the safety earth fails, it is difficult to discover this by direct measurement, because no phase has a voltage relative to earth. In the four-wire three-phase system, sometimes called "four-wire wye", the safety ground is connected to a neutral wire that is physically connected to the zero-voltage side of the three windings of the generator or transformer. Since all power phases are relative to the neutral in this system, if the neutral is disconnected, it can be directly measured.

In the United States, the National Electrical Code requires neutrals to be of this type. In this system, power meters measure and sum all three phases relative to the neutral. In North America, it is common for electricity meters to plug into a standardised socket outdoors, on the side of a building. This allows the meter to be replaced without disturbing the wires to the socket, or the occupant of the building. Some sockets may have a bypass while the meter is removed for service.

The amount of electricity used without being recorded during this small time is considered insignificant when compared to the inconvenience which might be caused to the customer by cutting off the electricity supply. Most electronic meters in North America use a serial protocol, ANSI C12.18. In many other countries the supply and load terminals are in the meter housing itself. Cables are connected directly to the meter. In some areas the meter is outside, often on a utility pole. In others, it is inside the building in a niche.

If inside, it may share a data connection with other meters. If it exists, the shared connection is often a small plug near the post box. The connection is often EIA-485 or infrared with a serial protocol such as IEC 62056. In 2014, networking to meters is rapidly changing. The most common schemes seem to combine an existing national standard for data (e.g. ANSI C12.19 or IEC 62056) operating via the Internet Protocol with a small circuit board for powerline communication, or a digital radio for a mobile phone network, or an ISM band.

Global standards for Electricity Metering

Electricity meters are governed by various standards worldwide to ensure accuracy, reliability, and interoperability. These standards vary by region and are often based on national or international regulations. Below are the key standards used in different regions. European Standards In Europe, electricity meters are primarily regulated under the Measuring Instruments Directive (MID), established by the European Union. MID ensures that electricity meters meet specific technical and operational criteria for accurate billing.

Key standards include: EN 50470-1 to EN 50470-3: These standards specify general requirements, particular requirements, and tests for active energy meters. IEC 62052 and IEC 62053 series: Commonly applied for the functional and accuracy performance of electricity meters. American Standards In the United States, the standards are developed by the American National Standards Institute (ANSI) and the Institute of Electrical and Electronics Engineers (IEEE).

Key standards include: ANSI C12 Series: Covering meter accuracy, testing, and performance for residential, commercial, and industrial meters. IEEE 1708: Provides guidelines for testing the cybersecurity of smart meters. Chinese Standards In China, electricity meter standards are governed by the China National Standards (GB), which align with international practices but also reflect specific local requirements: GB/T 17215: Sets the requirements for static electricity meters for active energy.

DL/T 645: Specifies the communication protocol for multi-function electricity meters, ensuring interoperability. Australian Standards In Australia, electricity meters adhere to the standards set by Standards Australia and the National Measurement Institute (NMI): AS 62052.11 and AS 62053.21: Align with IEC standards for general requirements and accuracy classes of electricity meters. NMI M 6: Specifies the metrological requirements for electricity meters used for billing.