Immersion cooling

Immersion cooling is a method where electronic parts or whole servers are put into a special, electrically safe liquid for cooling.

Uses your system voice; voice and rate in settings.

Snapshot

≈ 7 min read

Names in other languages

No names in other languages are held for this entry yet.

Article bodies are English and are not machine-translated. A name in another language is not a translation of the article.

Immersion cooling is a method where electronic parts or whole servers are put into a special, electrically safe liquid for cooling. The liquid removes heat much faster than air, which lowers energy costs, prevent noisy fans being used, and allows more heat-generating computer components in a tight space.

This includes systems using single-phase or two-phase dielectric liquids, leveraging their thermal capabilities to manage and dissipate heat generated by electronic components. Heat is removed from the system by putting the coolant in direct contact with hot components, and circulating the heated liquid through heat exchangers.

This practice is highly effective as liquid coolants can absorb more heat from the system than air. Immersion cooling has many benefits, including but not limited to: sustainability, performance, reliability, and cost. The fluids used in immersion cooling are dielectric liquids to ensure that they can safely come into contact with energized electronic components.

Commonly used dielectric liquids in immersion cooling are synthetic hydrocarbons, esters (natural and synthetic) and fluorochemicals.

Dielectric liquids

In general, the dielectric liquids used for immersion cooling fall into the following categories: synthetic hydrocarbons (synthetic oils), esters (natural and synthetic) and fluorochemicals. (fully engineered liquids). Dielectric liquids are divided into single- and two-phase applications, which differ in whether or not the cooling fluid turns into a gas during the cooling cycle.

Single-phase immersion circulates the dielectric liquid, which takes the heat, flows to a cooler part where it transfers the heat to the cooler then moves back the cooled liquid to the electronics. A single-phase fluid does not boil or undergo a phase change at any time during the cooling process.

Two-phase immersion uses a dielectric liquid with low boiling temperature (typically fluorocarbons), which boils and the hot gas rises to a cooling plate, where the gas transfers its heat to the cooler and gets transferred back to the electronics as liquid again. This method transfers heat more effectively than single-phase systems.

Forms

An enclosed chassis is an Immersion solution type with which dielectric liquid is circulated through a sealed server chassis. This requires (dripless) connectors to interface to the individual chassis. These chassis are typically aimed at traditional rack style placement of systems.

The connectors usually require a small closed-circuit cooling loop with a coolant to protect the flow integrity through pipes and connectors. The closed circuit is facilitated by a Coolant Distribution Unit (CDU), which may facilitate multiple racks at once.

An open bath refers to the "open" liquid–air interface and thus surface tension between the liquid and the air is a distinctive element. Open bath systems are usually tanks which contain a larger body of dielectric liquid where electronics are immersed into the bath. Multiple electronic assemblies share the same liquid.

Regardless of the term, open-bath systems can be fully sealed (especially with 2-phase immersion), but are always opened from the top to service IT equipment. The tank for open bath immersion systems is either connected to a CDU which circulates the dielectric liquid, or contains an integrated heat exchanging device which is part of the tank, to facilitate heat rejection to (typically) the Facility Water System (FWS).

For a facility interface, CDUs are usually designed for 100 kW or more, whereas an integrated heat exchanging device is usually designed for 10-100 kW cooling capacity. Hybrid cooling refers to combinations of enclosed and open bath apparatus and the use of cold plate technology in immersion.

History

19th and 20th century immersion milestones: Immersing electric systems (specifically transformers) in dielectric fluids for thermal management was used before 1887. The first patent to explicitly mention the use of oil as a coolant and insulator is in the patent submitted for a Constant Current Transformer in 1899 by Richard Fleming of Lynn, Massachusetts, assignor to the General Electric Company of New York Since the 1950s, power vacuum tubes with anode voltages above 100 kV were immersed in transformer oil The first reference to the specific use of dielectric fluids being used to cool "computers" is in 1966 by Oktay Sevgin of IBM.

In 1968, Richard C. Chu and John H. Seely, working for IBM patented an "Immersion cooling system for modularly packaged components." Seymour R. Cray Jr. founder of Cray Research, LLC patented a "Immersion cooled high density electronic assembly" in 1982.

The Cray T90 (released in 19951) used large liquid-to-chilled-liquid heat exchangers and single or two-phase immersion cooling liquids for heat removal Due to the arrival of CMOS, significant energy savings were achieved in CPUs which rapidly reduced the cooling challenges of HPC systems. It was not until the second decade that immersion regained traction due to increasing thermal properties of chips.

21st century immersion milestones: Starting in 2016, the rise of cryptocurrency becomes a main and significant driving force behind immersion. This is due to the high TCO advantages which are highly valued in crypto mining. This period has allowed many immersion technologies to gain essential experience and mature their technologies.

2017 shows a large volume of start-ups in the immersion cooling domain. Mostly related to cryptocurrency and the increasing power and cooling challenges in the datacenter industry. In 2018, the Open Compute Project officially embraces immersion in a new project under Rack & Power as part of ACS (Advanced Cooling Solutions).

In 2019, the first documented industry standards for immersion are presented at the OCP summit in San Jose. In 2020, Telecommunications Industry Association publishes their first mention of Immersion Cooling as a viable cooling option.

Domestic or process heating

Since 2016, immersion cooling in particular for bitcoin mining has become a popular method to generate usable heat. Immersion cooling offered a means to silently convert the waste heat from the mining operation to heat water, melt snow, power in-floor heating, and heat hot tubs, pools, shops, outbuildings, sheds, and greenhouses.

There is a compelling case to combine bitcoin mining operations with indoor vertical farms and traditional greenhouses to offset or eliminate the heating cost of the facilities. Indoor and outdoor recreation facilities both public and private can also benefit from the "free" waste heat. Some companies provide computing-based heating for residential and commercial operations.

Immersion Cooling of Li-Ion Battery

Overheating of Li-ion cells and battery packs is an ongoing technological challenge for electrochemical energy conversion and storage, including in electric vehicles. Immersion cooling is a promising thermal management technique to address these challenges.

Immersion cooling of batteries is specifically beneficial in abuse conditions, where the thermal propagation is needed to be avoided across the battery module or pack . Immersion cooling is gaining prominence as an emerging application within the industries of grid battery and automotive.

With a heat transfer capability 50 to 100 times greater than indirect cooling methods, immersion cooling stands out as an efficient and powerful solution. Presently, immersion cooling is predominantly utilized in motorsport and high-end vehicle models, showcasing its effectiveness in cutting-edge automotive technologies.

See also

Liquid dielectric Hydrofluoroether Novec 649

Text derived from https://en.wikipedia.org/w/index.php?oldid=1367991052 under CC BY-SA 4.0; modifications have been made.