Synchronverters (also called virtual synchronous generators or virtual synchronous machines) are inverters which mimic synchronous generators (SG) to provide "synthetic inertia" for ancillary services in electric power systems. Inertia is a property of standard synchronous generators associated with the rotating physical mass of the system spinning at a frequency proportional to the electricity being generated.
Inertia has implications towards grid stability as work is required to alter the kinetic energy of the spinning physical mass and therefore opposes changes in grid frequency. Inverter-based generation inherently lacks this property as the waveform is being created artificially via power electronics.
Synchronverters (also called virtual synchronous generators or virtual synchronous machines) are inverters which mimic synchronous generators (SG) to provide "synthetic inertia" for ancillary services in electric power systems. Inertia is a property of standard synchronous generators associated with the rotating physical mass of the system spinning at a frequency proportional to the electricity being generated.
Inertia has implications towards grid stability as work is required to alter the kinetic energy of the spinning physical mass and therefore opposes changes in grid frequency. Inverter-based generation inherently lacks this property as the waveform is being created artificially via power electronics.
Synchronverter model
Synchronverter structure can be divided into two parts: power part (see figure 2) and electronic part. The power part is energy transform and transfer path, including the bridge, filter circuit, power line, etc. The electronic part refers to measuring and control units, including sensors and digital signal processor (DSP).
The important point in modeling synchronverter is to be sure that it has similar dynamic behavior to Synchronous generator (see figure 3). This model is classified in increasing order of complexity, from 2-order (i.e. electromechanical model, typically derived from the swing equation) up to 7-order model (i.e. including transient, full rotor and stator dynamics).
However, 3-order model is widely used because of proper compromise between accuracy and complexity, which combined the electromechanical model with a voltage dynamics equation for one of the flux linkages (typically the q-axis). The dq-axes components the terminal voltage satisfy the following differential equations: V_{d}(t) = -R_{s}i_{d} - \frac{d\lambda_{d}}{dt} - \omega \lambda_{q}, V_{q}(t) = -R_{s}i_{q} - \frac{d\lambda_{q}}{dt} + \omega \lambda_{d}, where the flux linkages are \lambda_{d} = L_{d}i_{d} + \sqrt{3/2}M_{f}i_{f}, \lambda_{q} = L_{q}i_{q}, with \{i_{d},i_{q}\} representing the current as a function of time, R_{s} the stator resistance, \omega the angular velocity of the rotating reference frame, \{L_{d},L_{q}\} the inductances, M_f i_f represents the flux linkage from the rotor field winding and \{-\omega \lambda_d,\omega\lambda_q\} are the rotational emfs or speed voltages internal to the machine due to the rotation of the rotor (i.e. the dq-transformation of the stator reference frame).
While synchronverter terminal voltage and current satisfy these equations, synchronverter can be looked as Synchronous generator. This make it possible to replace it by a synchronous generator model and solve the problems easily.
Control strategy
As shown in the figure 3, when the inverter is controlled as a voltage source, it consists of a synchronization unit to synchronize with the grid and a power loop to regulate the real power and reactive power exchanged with the grid. The synchronization unit often needs to provide frequency and amplitude.
But when inverter is controlled as a current source, the synchronization unit is often required to provide the phase of the grid only, so it is much easier to control it as a current source. Since a synchronous generator is inherently synchronized with the grid, it is possible to integrate the synchronization function into the power controller without synchronization unit.
This results in a compact control unit, as shown in the figure 4.
PV
Synchronverters can be treated like synchronous generator, which make it easier to control the source, so it could be widely used in PV primary energy sources (PES).
HVDC
Source:
Wind turbine
Source:
DC microgrid
Synchronverter also is suggested to be used in microgrids because DC sources can be coordinated together with the frequency of the ac voltage, without any communication network.
Battery reserve
As demonstrated by the Hornsdale Power Reserve in Australia