Inrush current

Inrush current, input surge current, or switch-on surge is the maximal instantaneous input current drawn by an electrical device when first turned on.[src] Alternating-current electric motors and transformers may draw several times their normal full-load current when first energized, for a few cycles of the input waveform.[src] Power converters also often have inrush currents much higher than their steady-state currents, due to the charging current of the input capacitance.[src] The selection of over-current-protection devices such as fuses and circuit breakers is made more complicated when high inrush currents must be tolerated.[src] The over-current protection must react quickly to overload or short-circuit faults but must not interrupt the circuit when the (usually harmless) inrush current flows.[src]

Inrush current, input surge current, or switch-on surge is the maximal instantaneous input current drawn by an electrical device when first turned on.[src] Alternating-current electric motors and transformers may draw several times their normal full-load current when first energized, for a few cycles of the input waveform.[src] Power converters also often have inrush currents much higher than their steady-state currents, due to the charging current of the input capacitance.[src] The selection of over-current-protection devices such as fuses and circuit breakers is made more complicated when high inrush currents must be tolerated.[src] The over-current protection must react quickly to overload or short-circuit faults but must not interrupt the circuit when the (usually harmless) inrush current flows.[src] ==Capacitors== A discharged or partially charged capacitor appears as a short circuit to the source when the source voltage is higher than the potential of the capacitor.[src] A fully discharged capacitor will take approximately 5 RC time periods to fully charge; during the charging period, instantaneous current can exceed steady-state current by a substantial multiple.[src] Instantaneous current declines to steady-state current as the capacitor reaches full charge.[src] In the case of open circuit, the capacitor will be charged to the peak AC voltage (one cannot actually charge a capacitor with AC line power, so this refers to a varying but unidirectional voltage; e.g., the voltage output from a rectifier).[src] In the case of charging a capacitor from a linear DC voltage, like that from a battery, the capacitor will still appear as a short circuit; it will draw current from the source limited only by the internal resistance of the source and ESR of the capacitor.[src] In this case, charging current will be continuous and decline exponentially to the load current.[src] For open circuit, the capacitor will be charged to the DC voltage.[src] Safeguarding against the filter capacitor’s charging period’s initial current inrush flow is crucial for the performance of the device.[src] Temporarily introducing a high resistance between the input power and rectifier can increase the resistance of the powerup, leading to reducing the inrush current.[src] Using an inrush current limiter for this purpose helps, as it can provide the initial resistance needed.[src] ==Transformers== When a transformer is first energized, a transient current up to 10 to 15 times larger than the rated transformer current can flow for several cycles.[src] Toroidal transformers, using less copper for the same power handling, can have up to 60 times inrush to running current.[src] Worst-case inrush happens when the primary winding is connected at an instant around the zero crossing of the primary voltage (which for a pure inductance would be the current maximum in the AC cycle) and if the polarity of the voltage half-cycle has the same polarity as the remanence in the iron core has (the magnetic remanence was left high from a preceding half cycle).[src] Unless the windings and core are sized to normally never exceed 50% of saturation (and in an efficient transformer they never are, such a construction would be overly heavy and inefficient), then during such a start-up the core will be saturated.[src] This can also be expressed as the remnant magnetism in normal operation is nearly as high as the saturation magnetism at the "knee" of the hysteresis loop.[src] Once the core saturates, however, the winding inductance appears greatly reduced, and only the resistance of the primary-side windings and the impedance of the power line are limiting the current.[src] As saturation occurs for part half-cycles only, harmonic-rich waveforms can be generated and can cause problems to other equipment.[src] For large transformers with low winding resistance and high inductance, these inrush currents can last for several seconds until the transient has died away (decay time proportional to X L /R) and the regular AC equilibrium is established.[src] To avoid magnetic inrush, only for transformers with an air gap in the core, the inductive load needs to be synchronously connected near a supply voltage peak, in contrast with the zero-voltage switching, which is desirable to minimize sharp-edged current transients with resistive loads such as high-power heaters.[src] But for toroidal transformers only a premagnetising procedure before switching on allows to start those transformers without any inrush-current peak.[src] Inrush current can be divided in three categories: Energization inrush current result of re-energization of transformer.[src] The residual flux in this case can be zero or depending on energization timing.[src] Recovery inrush current flow when transformer voltage is restored after having been reduced by system disturbance.[src] Sympathetic inrush current flow when multiple transformer connected in same line and one of them energized.[src] ==Motors== When an electric motor, AC or DC, is first energized, the rotor is not moving, and a current equivalent to the stalled current will flow, reducing as the motor picks up speed and develops a back EMF to oppose the supply.[src] AC induction motors behave as transformers with a shorted secondary until the rotor begins to move, while brushed motors present essentially the winding resistance.[src] The duration of the starting transient is less if the mechanical load on the motor is relieved until it has picked up speed.[src] For high-power motors, the winding configuration may be changed (wye at start and then delta) during start-up to reduce the current drawn.[src] ==Heaters and filament lamps== Metals have a positive temperature coefficient of resistance; they have lower resistance when cold.[src] Any electrical load that contains a substantial component of metallic resistive heating elements, such as an electric kiln or a bank of tungsten-filament incandescent bulbs, will draw a high current until the metallic element reaches operating temperature.[src] For example, wall switches intended to control incandescent lamps will have a "T" rating, indicating that they can safely control circuits with the large inrush currents of incandescent lamps.[src] The inrush may be as much as 14 times the steady-state current and may persist for a few milliseconds for smaller lamps up to several seconds for lamps of 500 watts or more.[src] (Non-graphitized) carbon-filament lamps, rarely used now, have a negative temperature coefficient and draw more current as they warm up; an "inrush" current is not found with these types.[src] ==Protection== A resistor in series with the line can be used to limit the current charging input capacitors.[src] However, this approach is not very efficient, especially in high-power devices, since the resistor will have a voltage drop and dissipate some power.[src] Inrush current can also be reduced by inrush current limiters.[src] Negative-temperature-coefficient (NTC) thermistors are commonly used in switching power supplies, motor drives and audio equipment to prevent damage caused by inrush current.[src] A thermistor is a thermally-sensitive resistor with a resistance that changes significantly and predictably as a result of temperature changes.[src] The resistance of an NTC thermistor decreases as its temperature increases.[src] As the inrush current limiter self-heats, the current begins to flow through it and warm it.[src] Its resistance begins to drop, and a relatively small current flow charges the input capacitors.[src] After the capacitors in the power supply become charged, the self-heated inrush current limiter offers little resistance in the circuit, with a low voltage drop with respect to the total voltage drop of the circuit.[src] A disadvantage is that immediately after the device is switched off, the NTC resistor is still hot and has a low resistance.[src] It cannot limit the inrush current unless it cools for more than 1 minute to get a higher resistance.[src] Another disadvantage is that the NTC thermistor is not short-circuit-proof.[src] Another way to avoid the transformer inrush current is a "transformer switching relay".[src] This does not need time for cool down.[src] It can also deal with power-line half-wave voltage dips and is short-circuit-proof.[src] This technique is important for IEC 61000-4-11 tests.[src] Another option, particularly for high-voltage circuits, is to use a pre-charge circuit.[src] The circuit would support a current-limited precharge mode during the charging of capacitors and then switch to an unlimited mode for normal operation when the voltage on the load is 90% of full charge.[src] ==Switch-off spike== When a transformer, electric motor, electromagnet, or other inductive load is switched off, the inductor increases the voltage across the switch or breaker and can cause extended arcing.[src] When a transformer is switched off on its primary side, inductive kick produces a voltage spike on the secondary that can damage insulation and connected loads.[src] ==See also== Ripple (electrical) ==References== ==External links== IEC 61000–4–30, Electromagnetic Compatibility (EMC) – Testing and measurement techniques – Power quality measurement methods, Published by The International Electrotechnical Commission, 2003.[src]

64 sentences · 64 cited inline · 0 references stored

References

No reference rows published for this article.

Cite this article

MLA

"Inrush current." encyclopegia.org, 2025, https://encyclopegia.org/wiki/inrush-current. Accessed 25 November 2026.

Chicago

"Inrush current." encyclopegia.org. Accessed November 25, 2026. https://encyclopegia.org/wiki/inrush-current.

APA

encyclopegia.org. (2025). Inrush current. Retrieved November 25, 2026, from https://encyclopegia.org/wiki/inrush-current

Accessed November 25, 2026 · CC BY-SA 4.0 · citation page · JSON

Claims

PredicateValueSource
publication date2003Wikipedia

Related articles

electric current

stub · references available

Labrador Current

stub · references available

Falkland Current

stub · references available

eddy current

stub · references available

high-voltage direct current power line

stub · references available

pyroclastic density current

stub · references available

current asset

stub · references available

current account

stub · references available
CC BY-SA 4.0 · share-alike · https://en.wikipedia.org/w/index.php?oldid=1326751079 · 0.5 · snapshot enwiki-001326751079

Cite · JSON · Search

Related services and records

Services

  • Estate — measured countries, lanes and facts
  • Intel — live corroborated events
  • Legal — statutes, cases and citations
  • Encyclopedia — articles with inline sources
  • Space — launches, satellites and orbits
  • Search — federated search and reports
  • Pass — passport account and SSO
  • Corpora — read-only corpus origins
  • e01 — self-hosted corpora and tools

Text and metadata only; each target carries its own sources. Missing data is published as no-data, never estimated.