Per-unit system
In the power systems analysis field of electrical engineering, a per-unit system is the expression of system quantities as fractions of a defined base unit quantity.[src] Calculations are simplified because quantities expressed as per-unit do not change when they are referred from one side of a transformer to the other.[src] This can be a pronounced advantage in power system analysis where large numbers of transformers may be encountered.[src] Moreover, similar types of apparatus will have the impedances lying within a narrow numerical range when expressed as a per-unit fraction of the equipment rating, even if the unit size varies widely.[src] Conversion of per-unit quantities to volts, ohms, or amperes requires a knowledge of the base that the per-unit quantities were referenced to.[src] The per-unit system is used in power flow, short circuit evaluation, motor starting studies etc.[src] The main idea of a per unit system is to absorb large differences in absolute values into base relationships.[src] Thus, representations of elements in the system with per unit values become more uniform.[src] A per-unit system provides units for power, voltage, current, impedance, and admittance.[src] With the exception of impedance and admittance, any two units are independent and can be selected as base values; power and voltage are typically chosen.[src] All quantities are specified as multiples of selected base values.…[src]
In the power systems analysis field of electrical engineering, a per-unit system is the expression of system quantities as fractions of a defined base unit quantity.[src] Calculations are simplified because quantities expressed as per-unit do not change when they are referred from one side of a transformer to the other.[src] This can be a pronounced advantage in power system analysis where large numbers of transformers may be encountered.[src] Moreover, similar types of apparatus will have the impedances lying within a narrow numerical range when expressed as a per-unit fraction of the equipment rating, even if the unit size varies widely.[src] Conversion of per-unit quantities to volts, ohms, or amperes requires a knowledge of the base that the per-unit quantities were referenced to.[src] The per-unit system is used in power flow, short circuit evaluation, motor starting studies etc.[src] The main idea of a per unit system is to absorb large differences in absolute values into base relationships.[src] Thus, representations of elements in the system with per unit values become more uniform.[src] A per-unit system provides units for power, voltage, current, impedance, and admittance.[src] With the exception of impedance and admittance, any two units are independent and can be selected as base values; power and voltage are typically chosen.[src] All quantities are specified as multiples of selected base values.[src] For example, the base power might be the rated power of a transformer, or perhaps an arbitrarily selected power which makes power quantities in the system more convenient.[src] The base voltage might be the nominal voltage of a bus.[src] Different types of quantities are labeled with the same symbol (pu); it should be clear whether the quantity is a voltage, current, or other unit of measurement.[src] ==Purpose== There are several reasons for using a per-unit system: Similar apparatus (generators, transformers, lines) will have similar per-unit impedances and losses expressed on their own rating, regardless of their absolute size.[src] Because of this, per-unit data can be checked rapidly for gross errors.[src] A per unit value out of normal range is worth looking into for potential errors.[src] Manufacturers usually specify the impedance of apparatus in per unit values.[src] Use of the constant \textstyle \sqrt{3} is reduced in three-phase calculations.[src] Per-unit quantities are the same on either side of a transformer, independent of voltage level By normalizing quantities to a common base, both hand and automatic calculations are simplified.[src] It improves numerical stability of automatic calculation methods.[src] Per unit data representation yields important information about relative magnitudes.[src] The per-unit system was developed to make manual analysis of power systems easier.[src] Although power-system analysis is now done by computer, results are often expressed as per-unit values on a convenient system-wide base.[src] ==Relationship between units== The relationship between units in a per-unit system depends on whether the system is single-phase or three-phase.[src] ===Single-phase=== Assuming that the independent base values are power and voltage, we have: P_{\text{base}} = 1 \text{ pu} V_{\text{base}} = 1 \text{ pu} Alternatively, the base value for power may be given in terms of reactive or apparent power, in which case we have, respectively, Q_{\text{base}} = 1 \text{ pu} or S_{\text{base}} = 1 \text{ pu} The rest of the units can be derived from power and voltage using the equations S = IV , P = S\cos(\phi) , Q = S\sin(\phi) and \underline{V} = \underline{I} \underline{Z} (Ohm's law), Z being represented by \underline{Z} = R + j X = Z\cos(\phi) + j Z\sin(\phi) .[src] We have: I_{\text{base}} = \frac{S_{\text{base}}}{V_{\text{base}}} = 1 \text{ pu} Z_{\text{base}} = \frac{V_{\text{base}}}{I_{\text{base}}} = \frac{V_{\text{base}}^{2}}{I_{\text{base}}V_{\text{base}}} = \frac{V_{\text{base}}^{2}}{S_{\text{base}}} = 1 \text{ pu} Y_{\text{base}} = \frac{1}{Z_{\text{base}}} = 1 \text{ pu} ===Three-phase=== Power and voltage are specified in the same way as single-phase systems.[src] However, due to differences in what these terms usually represent in three-phase systems, the relationships for the derived units are different.[src] Specifically, power is given as total (not per-phase) power, and voltage is line-to-line voltage.[src] In three-phase systems the equations P = S\cos(\phi) and Q = S\sin(\phi) also hold.[src] The apparent power S now equals S_{\text{base}}= \sqrt{3}V_{\text{base}} I_{\text{base}} I_{\text{base}} = \frac{S_{\text{base}}}{V_{\text{base}} \times \sqrt{3}} = 1 \text{ pu} Z_{\text{base}} = \frac{V_{\text{base}}}{I_{\text{base}} \times \sqrt{3}} = \frac{{V_{\text{base}}^2}}{S_{\text{base}}} = 1 \text{ pu} Y_{\text{base}} = \frac{1}{Z_{\text{base}}} = 1 \text{ pu} ==Example of per-unit== As an example of how per-unit is used, consider a three-phase power transmission system that deals with powers of the order of 500 MW and uses a nominal voltage of 138 kV for transmission.[src] We arbitrarily select S_{\mathrm{base}} = 500\, \mathrm{MVA} , and use the nominal voltage 138 kV as the base voltage V_{\mathrm{base}} .[src] We then have: I_{\text{base}} = \frac{S_{\text{base}}}{V_{\text{base}} \times \sqrt{3}} = 2.09 \, \mathrm{kA} Z_{\text{base}} = \frac{V_{\text{base}}}{I_{\text{base}} \times \sqrt{3}} = \frac{V_{\text{base}}^{2}}{S_{\text{base}}} = 38.1 \, \Omega Y_{\mathrm{base}} = \frac{1}{Z_{\mathrm{base}}} = 26.3 \, \mathrm{mS} If, for example, the actual voltage at one of the buses is measured to be 136 kV, we have: V_{\mathrm{pu}} = \frac{V}{V_{\mathrm{base}}} = \frac{136 \, \mathrm{kV}}{138 \, \mathrm{kV}} = 0.9855 \, \mathrm{pu} ==Per-unit system formulas== The following tabulation of per-unit system formulas is adapted from Beeman's Industrial Power Systems Handbook.[src] E_\text{1,pu}&=\frac{E_{1}}{V_\text{base1}}\\ &= \frac {N_{1}E_{2}}{N_{2}V_\text{base1}} \\ &= \frac {N_{1}E_{2}}{N_{2} \frac{N_{1}}{N_{2}} V_\text{base2}}\\ &= \frac {E_{2}} {V_\text{base2}}\\ &= E_\text{2,pu}\\ \end{align} (source: Alexandra von Meier Power System Lectures, UC Berkeley) E 1 and E 2 are the voltages of sides 1 and 2 in volts.[src] N 1 is the number of turns the coil on side 1 has.[src] N 2 is the number of turns the coil on side 2 has.[src] V base1 and V base2 are the base voltages on sides 1 and 2.[src] V_\text{base1}=\frac{N_{1}}{N_{2}}V_\text{base2} For current, we can prove that the per-unit currents of the two sides are the same below.[src] \begin{align} I_\text{1,pu}&=\frac{I_{1}}{I_\text{base1}}\\ &= \frac {N_{2}I_{2}}{N_{1}I_\text{base1}} \\ &= \frac {N_{2}I_{2}}{N_{1} \frac{N_{2}}{N_{1}} I_{base2}}\\ &= \frac {I_{2}} {I_\text{base2}}\\ &= I_\text{2,pu}\\ \end{align} (source: Alexandra von Meier Power System Lectures, UC Berkeley) where I 1,pu and I 2,pu are the per-unit currents of sides 1 and 2 respectively.[src] In this, the base currents I base1 and I base2 are related in the opposite way that V base1 and V base2 are related, in that \begin{align} I_\text{base1} &= \frac{S_\text{base1}} {V_\text{base1}}\\ S_\text{base1} &= S_\text{base2}\\ V_\text{base2} &= \frac{N_{2}}{N_{1}} V_\text{base1}\\ I_\text{base2} &= \frac{S_\text{base2}} {V_\text{base2}}\\ I_\text{base1} &= \frac{S_\text{base2}} { \frac{N_{1}}{N_{2}} V_\text{base2}}\\ &= \frac{N_{2}}{N_{1}} I_\text{base2}\\ \end{align} The reason for this relation is for power conservation S base1 = S base2 The full load copper loss of a transformer in per-unit form is equal to the per-unit value of its resistance: \begin{align} P_\text{cu,FL}&=\text{full-load copper loss}\\ &= I_{R1}^2R_{eq1}\\ \end{align} \begin{align} P_\text{cu,FL,pu}&=\frac{P_\text{cu,FL}}{P_\text{base}}\\ &= \frac {I_{R1}^2R_{eq1}} {V_{R1}I_{R1}}\\ &= \frac {R_\text{eq1}} {V_{R1}/I_{R1}}\\ &= \frac {R_\text{eq1}} {Z_{B1}}\\ &= R_\text{eq1,pu}\\ \end{align} Therefore, it may be more useful to express the resistance in per-unit form as it also represents the full-load copper loss.[src] As stated above, there are two degrees of freedom within the per unit system that allow the engineer to specify any per unit system.[src] The degrees of freedom are the choice of the base voltage (V ) and the base power (S ).[src] By convention, a single base power (S ) is chosen for both sides of the transformer and its value is equal to the rated power of the transformer.[src] By convention, there are actually two different base voltages that are chosen, V and V which are equal to the rated voltages for either side of the transformer.[src] By choosing the base quantities in this manner, the transformer can be effectively removed from the circuit as described above.[src] For example: Take a transformer that is rated at 10 kVA and 240/100 V.[src] The secondary side has an impedance equal to 1∠0° Ω.[src] The base impedance on the secondary side is equal to: \begin{align} Z_\text{base,2}&=\frac{V_\text{base,2}^2}{S_\text{base}}\\ &= \frac {(100\text{ V})^2} {10000\text{ VA}}\\ &= \text{1 }\Omega\\ \end{align} This means that the per unit impedance on the secondary side is 1∠0° Ω / 1 Ω = 1∠0° pu When this impedance is referred to the other side, the impedance becomes: \begin{align} Z_{2}&=\left(\frac{240}{100}\right)^2\times\text{1∠0° }\Omega\\ &= \text {5.76∠0° }\Omega\\ \end{align} The base impedance for the primary side is calculated the same way as the secondary: \begin{align} Z_\text{base,1}&=\frac{V_\text{base,1}^2}{S_\text{base}}\\ &= \frac {(240\text{ V})^2} {10000\text{ VA}}\\ &= \text{5.76 }\Omega\\ \end{align} This means that the per unit impedance is 5.76∠0° Ω / 5.76 Ω = 1∠0° pu, which is the same as when calculated from the other side of the transformer, as would be expected.[src] Another useful tool for analyzing transformers is to have the base change formula that allows the engineer to go from a base impedance with one set of a base voltage and base power to another base impedance for a different set of a base voltage and base power.[src] This becomes especially useful in real life applications where a transformer with a secondary side voltage of 1.2 kV might be connected to the primary side of another transformer whose rated voltage is 1 kV.[src] The formula is as shown below.[src] \begin{align} Z_\text{pu,new}&=Z_\text{pu,old} \times \frac{Z_\text{base,old}}{Z_\text{base,new}}=Z_\text{pu,old} \times \left(\frac{V_\text{base,old}}{V_\text{base,new}}\right)^2\times\left(\frac{S_\text{base,new}}{S_\text{base,old}}\right)\\ \end{align} ==References==[src]
63 sentences · 63 cited inline · 0 references stored
References
No reference rows published for this article.
Cite this article
MLA
"Per-unit system." encyclopegia.org, 2025, https://encyclopegia.org/wiki/per-unit-system. Accessed 27 November 2026.
Chicago
"Per-unit system." encyclopegia.org. Accessed November 27, 2026. https://encyclopegia.org/wiki/per-unit-system.
APA
encyclopegia.org. (2025). Per-unit system. Retrieved November 27, 2026, from https://encyclopegia.org/wiki/per-unit-system
Accessed November 27, 2026 · CC BY-SA 4.0 · citation page · JSON